Efficiency Transformer, Power Transformer, Load Analysis, Transformer CapacityAbstract
Abstract — Power transformers are critical components in electrical distribution systems, serving to transmit electrical energy from substations to end-users. This study aims to analyze the load- handling capability of Power Transformer Unit 1 at the Paniki Substation in accommodating loads from feeders SN1 through SN5. The method involves collecting current and voltage data from the five feeders during February 2024, followed by load calculations compared against the transformer's rated capacity of 30 MVA. The results show that the total load reached 28.693 MVA, equivalent to approximately 95.7% of the transformer's capacity, which exceeds the optimal loading threshold of 80%. This indicates that the transformer is operating near its maximum capacity, potentially affecting system reliability. It is recommended to optimize the tap changer settings or consider upgrading the transformer capacity to maintain efficient and stable power distribution.
Key words — Efficiency Transformer, Power Transformer, Load Analysis, Transformer Capacity.
Abstrak — Transformator daya merupakan alat yang penting dalam sistem distribusi tenaga listrik yang berfungsi menyalurkan energi dari gardu induk ke pelanggan. Penelitian ini bertujuan untuk menganalisis kemampuan kapasitas transformator daya unit 1 di Gardu Induk Paniki dalam menangani beban dari penyulang SN1 hingga SN5, yang berlokasi di Paniki Atas, Kecamatan Talawaan, Kabupaten Minahasa Utara, Sukawesi Utara, Metode yang digunakan adalah pengumpulan data arus dan tegangan dari kelima penyulang selama bulan Februari 2024, kemudian dilakukan perhitungan beban dan dibandingkan dengan kapasitas nominal transformator sebesar 30 MVA. Hasil perhitungan menunjukkan bahwa pembebanan total mencapai 28,693 MVA atau sekitar 95,7% dari kapasitas trafo, yang melebihi batas optimal pembebanan sebesar 80%. Kondisi ini menunjukkan bahwa transformator berada dalam kondisi hampir jenuh, yang dapat berdampak terhadap keandalan sistem distribusi. Disarankan untuk melakukan pengaturan tap changer atau mempertimbangkan peningkatan kapasitas transformator guna menjaga kualitas penyaluran daya listrik secara berkelanjutan.
Kata kunci — Analisis Beban, Efisiensi Transfromatro, Transformator daya, kapasitas trafo
References
M. Solossa and H. Tasmono, “‘ANALISA EFISIENSI PADA TRANSFORMATOR DAYA 60 MVA DI GARDU INDUK BABADAN SIDOARJO,’” J. Ilm. Tek. dan Manaj. Ind., vol. 3, no. 2, pp. 1330–1338, 2023, doi: 10.46306/tgc.v3i2.
A. Monica Putri, P. Teknologi Rekayasa Pembangkit Energi Jl Medan-Banda Aceh Km, and B. Mangat, “STUDI PENGARUH PEMBEBANAN TERHADAP EFISIENSI TRANSFORMATOR 66 MVA DI PLTMG SUMBAGUT 2 PEAKER 250 MW,” J. TEKTRO, vol. 4, no. 2, p. 118, 2020.
H. Setijasa, dan Triyono, J. Teknik Elektro, and P. Negeri Semarang Jl Sudarto, “PERHITUNGAN EFISIENSI TRANSFORMATOR,” 2023.
M. Avif, A. H. Andriawan, and G. Dimas Prenata, “ANALISIS PEMBEBANAN TRANSFORMATOR DAYA 300 KVA DI INSTALASI PENGOLAHAN AIR LIMBAH PT. SIER,” 2022
S. Bahri, R. Gianto, M. Iqbal Arsyad, P. Studi Teknik Elektro, and J. Teknik Elektro, “Studi Pertambahan Beban Transformator Daya Pada Gardu Induk Parit Baru PT. PLN (Persero) Cabang Pontianak.”
R. Dwijayanti and T. Elektro, “PREDIKSI PEMBEBANAN PENYULANG TRANSFORMATOR DISTRIBUSI GARDU INDUK PETROKIMIA DENGAN METODE NONLINEAR AUTOREGRESSIVE NEURAL NETWORK (NARNN) Subuh Isnur Haryudo.”
R. Mahendra, A. Hiendro, P. Studi Teknik Elektro, and J. Teknik Elektro, “ANALISIS PENGARUH PEMBEBANAN TERHADAP EFISIENSI DAN UMUR TRANSFORMATOR PADA PLTU BENGKAYANG 2 × 50 MW PT. PLN (PERSERO) UPK SINGKAWANG.” Accessed: May 27, 2025. [Online]. Available: https://www.quipper.com/id/blog/mapel/fisika/transformator/
C. Bayu Pamungkas and I. Gatut Budiono, “ANALISA PEMBEBANAN TRANSFORMATOR DISTRIBUSI 500 KVA PT. POS INDONESIA SPP SURABAYA.”
H. Arif and E. B. Wahyono, “PENGARUH BEBAN PUNCAK TERHADAP EFISIENSI TRAFO DAYA”.
M. R. Hidayat and I. Fadilah, “Pengaruh Pembebanan Terhadap Efisiensi Transformator Distribusi Di PT. PLN (Persero) UP3 Garut,” SUTET, vol. 13, no. 1, pp. 1–12, Jul. 2023, doi: 10.33322/sutet.v13i1.1799.
M. R. Firmansyah, G. Budiono, and R. S. Widagdo, “Pengaruh Beban Puncak Terhadap Efisiensi Transformator 60 MVA di GIS 150/20 kV Simpang,” 2024.
S. Pamungkas, “ANALISIS PENGARUH BEBAN PUNCAK TERHADAP EFISIENSI TRANSFORMATOR 60 MVA
T. M. Asyadi and F. Moesnadi, “Volume 4 Nomor 2 Juli 2022”. 150/20KV UNIT 1 DAN 2 DI GARDU INDUK KALIWUNGU.”
C. S. M. ’Ahmad Nurhakim, “Transformator: Pengertian, Prinsip Kerja, Karakteristik, Hingga Contoh Soal,” Quipper Blog. Accessed: May 27, 2025. [Online]. Available: https://www.quipper.com/id/blog/mapel/fisika/transformator/
Risma Saputri, “Faktor-Faktor yang Mempengaruhi Efisiensi Transformator,” KAPITAREK. Accessed: May 27, 2025. [Online]. Available: https://www.kapitareka.com/artikel/faktor-faktor-yang-mempengaruhi-efisiensi-transformator/
Downloads
Published
Issue
Section
License
Copyright (c) 2025 Rivel Lewan, Lily S. Patras, Glanny M. Ch. Mangindaan (Author)

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

Jurnal Teknik Elektro dan Komputer is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.