Analysis of Grounding Resistance Reduction Using Counterpoise and Multi-Rod

Analisis Penurunan Tahanan Pentanahan dengan Counterpoise dan Multi-Rod

Authors

  • MUHAMMAD SOFIAN AZHARI Universitas Mataram Author
  • Rosmaliati Universitas Mataram Author

DOI:

https://doi.org/10.35793/f13qek55

Keywords:

Grounding resistance, counterpoise, Multi-Rod Grounding, transmission system, soil resistivity

Abstract

Abstract — This study aims to analyze the reduction of grounding resistance values in a 150 kV transmission tower using a combination of the counterpoise and multi-rod grounding methods. The main problem addressed is the high soil resistance that can reduce the reliability of the transmission system. The research was conducted on the 150 kV Peringabaya–Sambelia transmission line tower, specifically Tower 15, with measurements carried out on all four tower legs. The methodology included measuring the grounding resistance before and after improvement, as well as installing one additional grounding electrode on each tower leg. The results showed a significant reduction in grounding resistance values, from 103 Ω to 7 Ω (93.2%), 34.9 Ω to 7 Ω (79.9%), 36.9 Ω to 7 Ω (81.0%), and 165.3 Ω to 7 Ω (95.8%). All final resistance values met the required standard of less than 10 Ω. Therefore, the combination of the counterpoise and multi-rod grounding methods has proven effective in reducing grounding resistance and improving the reliability of electric power transmission systems.

Key words — Grounding resistance, counterpoise, Multi-Rod Grounding, transmission system, soil resistivity

 

Abstrak — Penelitian ini bertujuan untuk menganalisis penurunan nilai tahanan pentanahan pada menara transmisi 150 kV menggunakan kombinasi metode counterpoise dan Multi-Rod Grounding. Permasalahan yang dihadapi adalah tingginya tahanan pentanahan yang dapat memengaruhi keandalan sistem transmisi, khususnya dalam menghadapi gangguan akibat sambaran petir. Penelitian dilakukan pada Tower 15 SUTT 150 kV Peringabaya–Sambelia dengan melakukan pengukuran tahanan pentanahan pada empat kaki menara sebelum dan sesudah perbaikan. Perbaikan dilakukan dengan menambahkan elektroda batang pada setiap kaki menara serta memasang konduktor counterpoise secara horizontal sebagai jalur tambahan untuk memperluas area penyebaran arus ke tanah. Hasil pengukuran menunjukkan bahwa nilai tahanan pentanahan sebelum perbaikan pada kaki A, B, C, dan D masing-masing sebesar 103 Ω, 34,9 Ω, 36,9 Ω, dan 165,3 Ω. Setelah perbaikan, seluruh nilai tahanan pentanahan menjadi 7 Ω, dengan persentase penurunan masing-masing sebesar 93,2%, 79,9%, 81,0%, dan 95,8%. Hasil tersebut menunjukkan bahwa kombinasi metode counterpoise dan Multi-Rod Grounding mampu menurunkan nilai tahanan pentanahan pada Tower 15.

Kata kunci — Tahanan pentanahan, counterpoise, Multi-Rod Grounding, sistem transmisi, resistansi tanah

References

[1] S. Visacro, M. H. M. Vale, B. Pereira, and F. H. Silveira, “On the measurement of tower-footing impedance/resistance,” Electric Power Systems Research, vol. 234, Art. no. 110618, 2024.

[2] A. R. J. de Araújo, S. Kurokawa, C. M. Seixas, and B. Kordi, “Optimization of tower-footing grounding impedance for guyed-V transmission towers,” Electric Power Systems Research, vol. 177, Art. no. 105947, 2019.

[3] F. M. Gatta, A. Geri, S. Lauria, and M. Maccioni, “Backflashover simulation of HV transmission lines with enhanced counterpoise groundings,” Electric Power Systems Research, vol. 79, no. 7, pp. 1076–1084, 2009.

[4] W. L. M. de Azevedo, A. R. J. de Araújo, J. S. L. Colqui, J. L. A. D’Annibale, and J. Pissolato Filho, “Alternative study to reduce backflashovers using tower-footing grounding systems with multiple inclined rods,” Electric Power Systems Research, vol. 214, Art. no. 108893, 2023.

[5] B. Tang, Y. Huang, R. Liu, Z. Wu, and Z. Qu, “Fitting algorithm of transmission tower grounding resistance in vertically layered soil models,” Electric Power Systems Research, vol. 139, pp. 121–126, 2016 .

[6] N. M. Mucharomah, A. Nugroho, and S. Sumardi, “Analisis pemasangan multirod grounding pada ruas SUTT 70 kV Sunyaragi-Kuningan,” Jurnal Profesi Insinyur Indonesia, vol. 2, no. 1, pp. 26–31, 2024

[7] A. Faisal, M. Amril, J. Hidayat, and U. Hasnita, “Studi pengukuran tahanan pentanahan menara saluran udara tegangan tinggi (SUTT) 150 kV Sidikalang-Salak dengan menggunakan sistem counterpoise,” Journal of Electrical Technology, vol. 4, no. 3, pp. 130–134, 2019

[8] Y. Warmi and K. Michishita, “Tower-footing resistance and lightning trip-outs of 150 kV transmission lines in West Sumatra in Indonesia,” MATEC Web of Conferences, vol. 215, Art. no. 01022, 2018

[9] Y. Warmi, Zulkarnaini, A. Rajab, C. Yuanisa, R. O. Elyas, A. M. N. Putra, and Z. Anthony, “An optimal design of grounding system for tower footings in Payakumbuh 150 kV transmission line of Koto Panjang,” International Journal on Advanced Science, Engineering and Information Technology, vol. 13, no. 3, pp. 844–850, 2023.

[10] T. S. R. Muha, Y. Warmi, Z. Zulkarnaini, A. Y. Dewi, and E. Erhaneli, “Optimalisasi sistem pentanahan untuk mengurangi back flashover akibat sambaran petir pada tower SUTT penghantar Sentul-Cibinong,” Transmisi: Jurnal Ilmiah Teknik Elektro, vol. 27, no. 3, pp. 130–139, 2025.

[11] A. R. Idris et al., “Analisis pengaruh pemasangan counterpoise pada tower transmisi saluran udara tegangan tinggi 70 kV line Mandai–Pangkep,” in Prosiding Seminar Nasional Teknik Elektro dan Informatika (SNTEI), Makassar, Indonesia, 2021.

[12] R. P. Luntungan et al., “Analisa daerah lindung dan grounding pada tower transmisi akibat terjadinya back flashover,” Jurnal Teknik Elektro dan Komputer, vol. 7, no. 3, 2018.

[13] Darso et al., “Kelayakan sistem grounding pada gedung dan pemancar radio Be 107 FM,” Zona Elektro: Jurnal Ilmiah, vol. 15, no. 1, 2025.

[14] C. Andreansyah et al., “Studi kelayakan sistem grounding instalasi listrik pada Gedung Ulil Albab Uniska Kediri,” Zetroem, vol. 5, no. 1, 2023.

[15] H. Firnando et al., “Perancangan sistem proteksi petir eksternal di Gedung B Fakultas Sains dan Teknologi Universitas Jambi,” JITET (Jurnal Informatika dan Teknik Elektro Terapan), vol. 12, no. 3, 2024.

[16] PT PLN (Persero), Pedoman Pemeliharaan Saluran Udara Tegangan Tinggi (SUTT) dan Saluran Udara Tegangan Ekstra Tinggi (SUTET): Review dan Revisi KEPDIR No. 0520 K/DIR/2014. Jakarta, Indonesia: PT PLN (Persero), 2024.

[17] SPLN, Standar Perusahaan Listrik Negara tentang Pentanahan Sistem Tenaga Listrik. Jakarta, Indonesia: PT PLN (Persero), 2000.

[18] N. H. Saputro, “Analisis pentanahan kaki menara transmisi 150 kV Rembang–Blora bertahanan tinggi dan usaha menurunkannya,” Surakarta, Indonesia, 2016.

[19] A. Pranoto, H. Tumaliang, and G. M. C. Mangindaan, “Analisa sistem pentanahan gardu induk Teling dengan konstruksi grid (kisi-kisi),” Jurnal Teknik Elektro dan Komputer, vol. 7, no. 3, pp. 189–198, 2018.

Downloads

Published

2026-11-26